Features
● Low cost
● 4 standard sizes
● Split core design, safer, easier installation, and portable
Applications ● Measures AC current flow to electric motors,
lighting, air condition equipment, etc. Compatible with HVAC temperature control, power management, building automation systems.
Specifications ● Rated Primary current: 100-300Aac
● Rated Secondary: mA or 0.333-3.53Vac
● Accuracy: 0.5, 1.0, 3.0 Class
● Rated security coefficient: FS<5
● Case Material: nylon Resin UL flame retardant rating 94-V0
● Highest Voltage for Equipment Um (rms): 720 Vac
● Rated Power-Frequency Withstand Voltage (rms): 3,000 Vac
● Frequency Range: 50/60Hz.
● Operating Temperature: -15℃ to 60℃
● RoHS compliant
● Leads:0.8Foot(240mm),UL 1015,Twisted Pair,
0.34 mm2(22AWG)
Part Number |
Ratio |
Measuring |
Protection |
Frequency (Hz) |
Outline Dimensions ID-L-W-H (mm) |
pdf |
| Rated Input |
Accuracy Class |
Rated Accuracy Limit Primary Current (A) |
Accuracy Class |
|
| CTSA010 |
3000:1
|
5,10,20,50,75 |
1.0,3.0 |
120 |
5P,10P |
50~400 |
10 -29.4-26.4-41.7 |
| CTSA016 |
75,100,150 |
0.5,1.0 |
300 |
5P,10P |
50~400 |
16 -36.9-39.2-52.9 |
| CTSA024 |
100,150,200,250 |
0.5,1.0 |
540 |
5P,10P |
50~400 |
24 -51.2-47-70.2 |
| CTSA035 |
200,300,400,600 |
0.5,1.0 |
600 |
5P,10P |
50~400 |
35 -65.8-51.2-83.5 |